Skip to main content

GSME

for storage points, extraction + filter ­systems for the ­detection of ­combustion gases.

REMBE® GSME
Particularly plants that are at risk of explosive dust must frequently be provided with explosion protection measures, as ignition sources are often unavoidable. In addition to electrostatic phenomena and mechanically generated functions, the most frequent ignition sources particularly include glowing embers, open flames and hot surfaces. Alongside grounding monitoring systems and spark extinguishing systems, the GSME detector series make an enormous contribution to increasing explosion safety. The GSME series have been developed for the early identification of combustion reactions and thermal events, which can ultimately be ignition sources for explosions.
Application
The compact GSME pyrolysis gas detector is specifically tailored for the early detection of hot surfaces and fire in dust-handling equipment, such as silos, dryers, mills, conveyors or dust collectors.
REMBE® GSME mit Zubehör

Cable

Junction box

Advantages
  • Explosion prevention with early detection of smouldering and developing fires.
  • Highest moisture and dust resistance with unique diffusion filter technology.
  • Approvals in accordance with ATEX and IECEx.
  • Comprehensive explosion safety concepts through the integration of the detectors into the REMBE® EXKOP® Express control unit.
Funktionsweise GSME
Mechanism
The well-proven multi-criteria technology on a semiconductor basis already enables foolproof early detection by the GSME of all types of concealed and open glowing embers and smouldering fires in the emergent phase. The sensor elements of the detectors are protected from dust and moisture with the unique diffusion filter technology. The GSME is also protected from the penetration of moisture and dust due to its robust design. It is specifically designed for use in areas up to Zone 20 and tested in accordance with ATEX and IECEx.
Technical data
Mechanical properties
Housing
Coated die-cast aluminium (corrosion-resistant)
Dimensions (H x W x D)
100 x 152 x 100 mm (with cable gland and light module)
Weight
0.7 kg
Protection class
IP 64
Detection properties
Sensor combination
CO — H₂ — HC — NOx
Reaction time
> 30 s
Detection scenario
Smouldering fires according to EN 54/7, smouldering fires from various organic materials
Electrical properties
Voltage supply
20 to 40 V DC
Power consumption
10 VA
Internal fuse protection
750 mA
M-Bus Max. line length
≈ 2 km
M-Bus Max. line capacity
≈ 200 nF
M-Bus Baud rate
4800 baud
Limit value contact alarm relay
680 Ω , 20 mA max. (Alarm closer)
Limit value contact fault relay
0 Ω, 40 V or 20 mA max. (Fault opener)
Thermal properties
Relative humidity
0 to 99 % relative humidity (non-condensing)
Temperature
-20 to +50 °C
Applications + Industries
  • aerospace
  • animal feed productions
  • autoclaves
  • condensers
  • desalination plants
  • dual-fuel engines
  • elevators
  • flare stacks
  • food
  • LNG
  • mills and grinding plants
  • reactors
  • reverse osmosis systems
  • separators
  • silo
  • water injection pumps

Certifications

ATEX

ATEX

IECEx

IECEx

In contrast to conventional fire detection systems, the selection and positioning of special fire detectors is a particular challenge for industrial environments. The arrangement and alignment of the detectors should therefore be exclusively specified by specialist planners.

  • Click and drag image to view.
  • Scan the QR code with your iOS camera* to see an AR preview of the product.
    GSME AR Viewer Ru
    The dimensions shown may differ from those of the actual product.
    * Requires iOS 13, iPadOS 13, ARCore 1.9 or higher.
Your contact person
I will be happy to advise you about the most suitable Protection systems for your plant. Individually, in detail and taking all relevant parameters into ­account.
Alexander Kemmling | Sales Executive Explosion Prevention
Consulting. Engineering. Products. Service.
REMBE® GmbH Safety+Control
© REMBE® GmbH Safety+Control